AC PowerFor Business-Critical Continuity Liebert GXT3 208V, 5000-10,000VA, 6000RTL630User Manual
TABLE OF CONTENTS1.0INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42.0SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52.1Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 52.2Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.3Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.4Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.5DC-to-DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.6Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62.7Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63.0MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73.1Main Frame and Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.2Removable Power Distribution Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.3Internal Battery Packs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104.0WHAT’S INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115.0INSTALLATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125.1Install the Main Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125.1.15.1.25.1.3Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Rack-Mount UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Installing the Adjustable Rack-Mount Kit—Sold Separately . . . . . . . . . . . . . . . . . . . . . . . . . 135.2External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165.3Connect Input/Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175.3.15.3.25.3.35.3.45.3.5Remove the Power Distribution Box from 5000 and 6000VA Models . . . . . . . . . . . . . . . . . . .Remove the Power Distribution Cover from 8000 and 10,000VA Models . . . . . . . . . . . . . . . .Install the Power Distribution Box on 5000 and 6000VA Models . . . . . . . . . . . . . . . . . . . . . .Install the Power Distribution Box on 8000 and 10,000VA Models . . . . . . . . . . . . . . . . . . . .Distribution Box Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17181819195.4IT Power System Configuration—Liebert GXT3-6000RTL630 Only . . . . . . . . . . . . . . . . . . 216.0CONFIGURATION PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226.1Configuration Program Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226.1.1What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227.0CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237.1ON/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237.2Standby/Manual Bypass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237.3Load Level Indicators (4 Green, 1 Amber) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247.4Battery Level Indicators (5 Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247.5UPS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258.0OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .268.1Startup Checklist for the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268.2Initial Startup and Electrical Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268.3Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27i
8.4Put the Liebert GXT3 in Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278.5Shut Down the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278.6Disconnecting Input Power from the Liebert GXT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278.7Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279.0COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289.1Communication Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289.2Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289.2.19.2.29.2.39.2.49.3Any-Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28282929UPS IntelliSlot Communication Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299.3.1Liebert MultiLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309.4Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3010.0MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3110.1Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3110.2Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3210.3Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3210.4Checking UPS Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3310.5Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3310.6Replacing the Power Module on 8000 and 10,000VA models . . . . . . . . . . . . . . . . . . . . . . . . 3311.0TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3511.1UPS Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3510.1.1 Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3111.1.1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3511.1.2 Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3611.2Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3612.0SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3812.1Auto-Learning Battery Run Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44ii
FIGURESFigure 1Figure 2Figure 3Figure 4Figure 5Figure 6Figure 7Figure 8Figure 9Figure 10Figure 11Figure 12Figure 13Figure 14Figure 15Figure 16Figure 17Figure 18Figure 19Figure 20Figure 21Figure 22Figure 23Figure 24Figure 25Figure 26Liebert GXT3 front view—rack-mount and tower configurations . . . . . . . . . . . . . . . . . . . . . . . . . . 7Liebert GXT3 5000VA and 6000VA rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Input power hardwire boxes—5000 and 6000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Liebert GXT3-6000RTL630, rear view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Liebert GXT3 8000VA and 10,000VA rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Power distribution models for 5000VA and 6000VA models of Liebert GXT3 . . . . . . . . . . . . . . . . 9Power distribution models for 8000VA and 10,000VA models of Liebert GXT3 . . . . . . . . . . . . . . 10Internal battery pack features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Rotate the operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13External battery cabinets connected to 6000VA Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Power distribution box removal from 5000 and 6000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . 17Power distribution box removal from 8000 and 10,000VA models . . . . . . . . . . . . . . . . . . . . . . . . 18Distribution box electrical connections diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Terminal block connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Remove cover from IT Power System Connectors compartment . . . . . . . . . . . . . . . . . . . . . . . . . . 21Liebert GXT3 control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Load level indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Battery level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Terminal block communication pin layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Removing the front plastic bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Disconnecting the battery plug and battery receptacle (front view) . . . . . . . . . . . . . . . . . . . . . . . 31Pulling out the battery packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Removing power module from Liebert GXT3 8000 and 10,000VA models . . . . . . . . . . . . . . . . . . 34Battery level indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35TABLESTable 1Table 2Table 3Table 4Table 5Table 6Table 7Table 8Table 9Table 10Table 11Table 12Table 13Table 14Branch circuit breaker ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Indicator descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS specifications—5000, 6000, 8000 and 10,000 models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS specifications—Liebert GXT3-6000RTL630 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Internal battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .External battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Power distribution specifications: GXT3-5000RT208, GXT3-6000RT208 andGXT3-6000RTL630 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Power distribution box specifications for GXT3-8000RT208 and GXT3-10000RT208 . . . . . . . . .Battery run time, minutes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii1920253536363839404041414243
iv
IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important safety instructions. Read all safety and operating instructions beforeoperating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in thismanual. Follow all operating and user instructions. This equipment can be operated by individualswithout previous training.This product is designed for commercial/industrial use only. It is not intended for use with life supportand other designated “critical” devices. Maximum load must not exceed that shown on the UPS ratinglabel. The UPS is designed for data processing equipment. If uncertain, consult your dealer or localEmerson Network Power representative.This UPS is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230,120/208,120/240 or 127/220VAC, 50 or 60Hz supply. The factory default setting is 120/208VAC, 60Hz.Installation instructions and warning notices are in this manual.The GXT3 208VAC 5000 - 10000 is designed for use with a four-wire input (L1, L2, N, G).The GXT3-6000RTL630 is designed be used with a three-wire, two-phase utility source (L1, L2, G).!WARNINGThe battery can present a risk of electrical shock and high short circuit current. The followingprecautions should be observed when replacing the battery pack: Wear rubber gloves and bootsRemove rings, watches and other metal objects.Use tools with insulated handles.Do not lay tools or other metal objects on the batteries.If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson representative immediately. Do not dispose of batteries in a fire. The batteries may explode. Handle, transport and recycle batteries in accordance with local regulations.!WARNINGAlthough the Liebert GXT3 has been designed and manufactured to ensure personal safety,improper use can result in electrical shock or fire. To ensure safety, observe the followingprecautions: Turn Off and unplug the Liebert GXT3 before cleaning it.Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.Never block or insert any objects into the ventilation holes or other openings of the UPS.Do not place the Liebert GXT3 power cord where it might be damaged.1
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 complies with the limits for aClass A digital device, pursuant to Part 15 of FCC rules.Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interferencethat users must correct at their own expense.The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with theseinstructions and use of accessories approved by Emerson.NOTICEThis is a product for restricted sales distribution to informed partners. Installationrestrictions or additional measures may be needed to prevent radio interference.Operate the UPS in an indoor environment only in an ambient temperature range of 0-40 C(32-104 F). Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.The Liebert GXT3-5000RT208, Liebert GXT3-6000RT208 and the Liebert GXT3-6000RTL630 containno user-serviceable parts except the internal battery pack. The Liebert GXT3-10000RT208 and theLiebert GXT3-8000RT208 contain no user-serviceable parts except the internal battery pack and thePower Module. The UPS On/Off push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access internally due to the risk of electric shock or burn.Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or the UPS performance alters in use. Refer all faults to your dealer.Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries andthe required precautions. Keep unauthorized personnel away from the batteries. Keep unauthorizedpersonnel away from the batteries. Proper disposal of batteries is required. Refer to your local lawsand regulations for disposal requirements.Never block or insert any object into the ventilation holes or other openings.DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using halfwave rectification.Storing magnetic media on top of the UPS may result in data loss or corruption.Turn Off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.Information for the Protection of the EnvironmentUPS SERVICING—This UPS makes use of components dangerous for the environment (electroniccards, electronic components). The components removed must be taken to specialized collection anddisposal centers.2
GLOSSARY OF SYMBOLSRisk of electrical shock!Indicates caution followed by important instructionsAC inputAC outputi-Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid batteryPbH2SO4RRecycleDC voltageEquipment grounding conductorBonded to groundAC voltageON/Alarm Silence/Manual Battery TestOFF/BypassWEEE3
Introduction1.0INTRODUCTIONCongratulations on your choice of the Liebert GXT3 uninterruptible power system (UPS). The LiebertGXT3 comes in nominal power ratings of 5000VA, 6000VA, 8000VA and 10,000VA. It is designed toprovide conditioned power to microcomputers and other sensitive electronic equipment.When it is generated, alternating current is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete power failure that may interrupt computeroperations, cause data loss and even damage equipment. The Liebert GXT3 protects equipment fromthese disturbances.The Liebert GXT3 is a compact, on-line UPS. An on-line UPS continuously conditions and regulatesits output voltage, whether utility power is present or not. It supplies connected equipment withclean, sinewave power. Sensitive electronic equipment operates best from sinewave power.For ease of use, the Liebert GXT3 features a light-emitting diode (LED) display to indicate both loadpercentage and battery capacity. It also provides self-diagnostic tests, a combination ON/AlarmSilence/Manual Battery Test button, a Standby/Manual Bypass button and a configuration program.The Liebert GXT3 has a Liebert IntelliSlot port for communication between the UPS and a networkserver or other computer systems. This port provides detailed operating information includingvoltages, currents and alarm status to the host system when used in conjunction with LiebertMultiLink . Liebert MultiLink can also remotely control UPS operation.4
System Description2.0SYSTEM DESCRIPTIONOutputInputStaticBypassL1L2NL1TVSS erterBatteryChargerBatteryG2.1NGTransient Voltage Surge Suppression (TVSS) and EMI/RFI FiltersThese UPS components provide surge protection and filter both electromagnetic interference (EMI)and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.2.2Rectifier/Power Factor Correction (PFC) CircuitIn normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power toregulated DC power for use by the inverter while ensuring that the waveshape of the input currentused by the UPS is near ideal. Extracting this sinewave input current achieves two objectives: The utility power is used as efficiently as possible by the UPS. The amount of distortion reflected on the utility is reduced.This results in cleaner power being available to other devices in the building not being protected bythe Liebert GXT3.2.3InverterIn normal operation, the inverter utilizes the DC output of the power factor correction circuit andinverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverterreceives its required energy from the battery through the DC-to-DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC outputpower.2.4Battery ChargerThe battery charger utilizes energy from the utility power and precisely regulates it to continuouslyfloat charge the batteries. The batteries are being charged whenever the Liebert GXT3 is connected toutility power.2.5DC-to-DC ConverterThe DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.5
System Description2.6BatteryThe Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain batterydesign life, operate the UPS in an ambient temperature of 15 C to 25 C (59 F to 77 F). Optionalexternal battery cabinets are available to extend battery run times. For run times, see Table 14.2.7Dynamic BypassThe Liebert GXT3 provides an alternate path for utility power to the connected load in the unlikelyevent of a UPS malfunction. Should the UPS have an overload, overtemperature or any other UPSfailure condition, the UPS automatically transfers the connected load to bypass. Bypass operation isindicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated toindicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass,press the Standby/Manual Bypass button once and hold it for about 2 seconds.NOTEThe bypass power path does NOT protect the connected equipment from disturbancesin the utility supply.6
Major Components3.0MAJOR COMPONENTSThe Liebert GXT3 is composed of three major assemblies to provide easier handling, installation andversatility.3.1Main Frame and ElectronicsAll models of the Liebert GXT3 are shipped without the internal batteries installed. Power distribution varies by model and rating. Liebert GXT3 5000 and 6000VA models ship with a basic hardwire distribution box attached andready to be connected to the load (see Figure 2). Liebert GXT3RTL630 ships with a power distribution box attached (see (Figure 4). Liebert GXT3 8000 and 10,000VA models with a cover plate installed over connections for any ofseveral optional power distribution boxes (see Figure 5).Figure 1Liebert GXT3 front view—rack-mount and tower configurationsUpper BezelStatus Indicatorsand ControlsLower Bezel andBattery AccessDoorFigure 2Liebert GXT3 5000VA and 6000VA rear viewUSB PortREPOLiebertIntelliSlot PortKnockouts for HardwiredPower InputTerminal BlockCommunicationExternal BatteryConnectorInput BreakerFigure 3Input power hardwire boxes—5000 and 6000VA modelsMaintenanceBypass BreakerInputBreakerInput BreakerPD2-HDWR-MBS - 5000and 6000VA modelsPD2-HDWR5000 and 6000VA modelsNOTEHardwire and hardwire/receptacle boxes that include a manual bypass switch permit ACpower to continue to flow from the utility input to the load while the box is removed from theUPS. For details, refer to 3.2 - Removable Power Distribution Box.7
Major ComponentsFigure 4Liebert GXT3-6000RTL630, rear viewOutput Breaker forL6-20R #2 and #3REPO ConnectionBlockUSB PortTerminal BlockCommunicationOutput Breakerfor L6-30R #4ExternalBatteryConnectorLiebertIntelliSlot PortIT PowerSystemAccessCoverInput Breakerfor L6-30P #1Output Breakerfor L6-30R #5MaintenanceBypass Breaker1Figure 52543Liebert GXT3 8000VA and 10,000VA rear viewMaintenanceBypassSwitchLiebertIntelliSlot PortTerminal BlockCommunicationCover for PowerDistribution BoxConnectionsREPO Connection BlockUSB for HardwiredPower InputExternal BatteryConnector8
Major Components3.2Removable Power Distribution BoxThe UPS is shipped with a power distribution pack installed. This box contains the UPS input circuitbreaker.Figure 6Power distribution models for 5000VA and 6000VA models of Liebert GXT3MaintenanceBypass BreakerOutput Power Breakersfor PigtailsInput PowerBreakerPush Button OutputPower Breakers for TwoL5-20 Receptacles(second push buttonbreaker obscured)L14-30 InputPower ConnectorPD2-001 shown as example;similar features on other distributionboxes arranged differentlyPD2-002Receptacles: two 5-20R; two L6-20RPD2-001Receptacles: four 5-20; oneL14-30; one L6-30RPD2-005Receptacles: four L5-20R; two L6-30RPD2-006Receptacles: four L6-20RPD2-003receptacles: four 5-20R; two L6-30PD2-004Receptacles: four L5-20R; two L5-30R9
Major ComponentsFigure 7Power distribution models for 8000VA and 10,000VA models of Liebert GXT3p ;similar features on otherdistribution boxes arranged differently5-20R OutputReceptaclesOutput Circuit BreakerSwitch for L6-30R Pigtail #1L6-30ROutputReceptaclesPush ButtonCircuit Breakersfor 5-20RReceptacles25-20R OutputReceptaclesPD2-101Receptacles: two L6-30; eight 5-20R1Output Circuit BreakerSwitch for L6-30R Pigtail #2PD2-102Receptacles:four L6-20Rfour 5-20RPD2-105Receptacles:four 5-20Rtwo L5-30Rtwo L5-20RPD2-103Receptacles:four L6-30Rfour 5-20RPD2-106Receptacles:four L6-20Rfour L5-20RPD2-104Receptacles:four 5-20Rtwo L6-30Rtwo L6-20R3.3Internal Battery PacksThe UPS has two internal battery packs behind a battery access door on the front of the unit. Eachinternal battery pack is fitted with a connector to link to the UPS.Figure 8Internal battery pack featuresBattery HandleBattery ConnectorLiebert GXT3 8000 and 10,000VAbattery packs shown;5000 and 6000VA battery packshave same featuresFront of Battery Pack10
What’s Included4.0WHAT’S INCLUDEDThe Liebert GXT3 is shipped with the following items: Terminal Block Communication terminals Compact disc with: Liebert MultiLink Configuration program User manual (electronic version) USB cable, one; 2m (6-1/2 ft.) long Rack handles with mounting hardware Power Distribution Box, installed on Liebert GXT3 Plastic tower set, one Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)NOTEThe Liebert GXT3 External Battery Cabinet shipping package includes one battery cabinet, twospacers for the 5000 and 6000VA models and four spacers for the 8000 and 10000VA modelsfor tower configuration and one DC power cable.11
Installation and Configuration5.0INSTALLATION AND CONFIGURATIONDo NOT attempt to start the UPS, turn on any circuit breaker or energize the input power untilinstructed to do so in 8.2 - Initial Startup and Electrical Checks.Visually inspect the UPS for shipping damage. Report any damage to the carrier and your local dealeror Emerson representative.!CAUTIONThe UPS is heavy (see 12.0 - Specifications). Take proper precautions when liftingor moving it.Install the Liebert GXT3 indoors in a controlled environment, where it cannot be accidentally turnedoff. Place it where air flows unrestricted around the unit. The installation location must be free ofwater, flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front a
The Liebert GXT3-5000RT208, Liebert GXT3-6000RT208 and the Liebert GXT3-6000RTL630 contain no user-serviceable parts except the internal battery pack. The Liebert GXT3-10000RT208 and the Liebert GXT3-8000RT208 contain no user-serviceable parts except the internal battery pack and the Power Module.